S200: AC Input Drives Control and Power Specifications

NOTE: Unless otherwise specified, the specifications are worse-case limits and apply over the specified operating ambient temperature and over the specified operating line voltage.

AC Control Power Supply

Parameter
Rating
Input Voltage Range (RMS)
85 to 265 VAC single phase
47 to 63 Hz
120 to 375 VDC
Ride Through Time for AC Line Drop
85 VAC 60 Hz > 0.78 60 Hz cycles
120 VAC 60 Hz > 3.3 60 Hz cycles
240 VAC 60 Hz >18.5 60 Hz cycles

 

AC Motor Power Supply

Parameter
Rating
Input Voltage Range (RMS)
90 to 265 VAC
Phases
1 or 3
Transformer Suggested KVA
S20260: 1.5 to 2 kVA
S20360: 2.0 to 3 kVA
S20660: 3.0 to 5 kVA
Maximum AC Line KVA1
100
1 - Maximum AC Line is specified to limit the mains surges to the drive.

 

AC Bus Voltage and Faults

Parameter
Rating
240 VAC Input Nominal Bus Voltage
320 VDC
120 VAC Input Nominal Bus Voltage 155 VDC
BUS Undervoltage Fault Factory Default is None
BUS Overvoltge (BusOV) Fault 407 VDC ± 5%
BUS Regen Voltage
= 0.974 * BusOV = 397 VDC Nominal

 

AC Inrush Current and Fusing

Parameter
S20260
S20360
S20660
Worse Case Inrush Peak Current at 240 VAC
140 A 0-p 140 A 0-p 240 A 0-p
Inrush pulse width 1.5 ms 1.5 ms 2.0 ms

Recommended Fusing Line Inputs

Parameter
S20260
S20360
S20660
Type – 250 VAC Time Delay Fuse
   240 VAC 3 Phase (ARMS) Bussmann MDA-5 Bussmann MDA-8 Bussmann MDA-15
   240 VAC 1 Phase (ARMS) Bussmann MDA-5 Bussmann MDA-10 Bussmann MDA-20
   120 VAC 1 Phase (ARMS) Bussmann MDA-5 Bussmann MDA-10 Bussmann MDA-20

 

AC Control Inrush Current and Fusing

Parameter
Rating
Worse Case Inrush Peak Current at 240 VAC
10 A 0-p
Inrush Pulse Width 1.60 ms
Fusing – Control Inputs Bussmann MDA – 1/2

 

AC Power on Delay

Parameter
Rating
Control Power Applied to Drive Operational
1.25 sec

 