.

S200: Power Supply Design

Design

This section has additional considerations for DC power supplies.

Single Power Supply Operation

A single power supply can be used to provide main or motor power, and control power for the DC power input. The voltage range of a single supply is 20 V to 90 V.

NOTE: The drive can be damaged if the supply voltage exceeds 90 V, even briefly. The DC level plus transients plus regenerative pump up MUST NEVER exceed 90 V.

Wire the single supply +terminal to J1-3 (+Bus) and to J1-1 (+CTRL) and the power supply –terminal to J1-2 (Bus/Ctrl Gnd). This power supply is typically unregulated, but a regulated supply can also be used. The power supply outputs must be isolated from the power line. See Regulatory Information for more details on isolation requirements. Wire both the power supply negative terminal and the drive chassis to earth for safety.

The maximum continuous and peak (3 sec) main power and current at 75 V bus for the S200 DC drives is shown in the table below.

3/9 ARMS S200 DC
6/18 ARMS S200 DC
Main (continuous) 250 watts 500 watts
3.33 ADC at 75 V 6.67 ADC at 75 V
Main Peak (3 sec) 750 watts 1500 watts
10 ADC at 75 V 20 ADC at 75 V

The next figures provide representative connection diagrams and some detailed recommendations.


(Optional) Regulated, Isolated Supply


Wiring Multiple DC Drives

WARNING: An appropriately-sized output capacitor in the main power supply is the key to economically delivering high peak power. In most applications, the capacitor supplies much of the peak power needed to accelerate the motor and inertia (under 20 ms). It also lowers the cost of the supply by reducing its silicon current. In addition, it also absorbs regenerated energy with a limited pump up of voltage and stabilizes the bus voltage for better dynamics.

NOTE: While the maximum peak-to-continuous power capability ration is 3:1, most applications have much higher ratios. The requirement that the main supply have a high peak-to-continuous power ratio is very important in selecting or designing the power supply.

 

Main Supply Output Capacitance (J1-3 to J1-2)

The location of the main output capacitor is not critical. Up to 10 ft from the drive is an acceptable length, as long as the wire is sized so resistive drops at peak current are low. Voltage clipping of the inverter can cause the peak bus current to equal the motor current. A good rule is to size the bus wiring for 18 ARMS x rt(2) = 25.4 ARMS peak per drive. Use at least 16 AWG. The inductance of the bus and ground wiring is not critical because the internal drive bus capacitance can handle all the PWM current in most cases.

Servos put high peak power demands on the power supply. The easiest and best way to build a power supply to deliver and absorb pulses of peak power is for the supply to have an appropriately-sized output capacitor.

3/9 ARMS DC S200
6/18 ARMS DC S200
2000 µf / drive at 75 V bus 4000 µf / drive at 75 V bus
4000 µf / drive at 48 V bus 8000 µf / drive at 48 V bus
16000 µf / drive at 24 V bus 32000 µf / drive at 24 V bus

This can be the output capacitor of an unregulated power supply or a capacitor in parallel with the output of a regulated supply. In most cases, this capacitor does not need to be close to the drive, so a single capacitor can be shared by multiple drives. This capacitor does several jobs:

Bus capacitance absorbs net regenerated mechanical energy from the inertia when the motor decelerates.
If the bus capacitance is sufficient, regeneration causes a controlled, limited rise in bus voltage and the over-voltage fault is not tripped.

NOTE: If the regenerated mechanical energy is high, additional bus capacitors can be added in parallel. The bus capacitance can be increased almost without limit. The over-voltage fault is a non-latching fault that turns off the inverter transistors when the bus voltage is above the over-voltage threshold. An over-voltage fault trip interrupts the regeneration of mechanical energy back to the bus. This limits the bus voltage rise and protects the drive. However, it interrupts motor torque, so the machine cycle is affected. In most cases it is undesirable to allow the bus voltage to pump up to the over-voltage fault threshold.

In many applications, much or all of the rotational mechanical energy is dissipated as heat in the motor windings when the motor decelerates. The maximum regenerated rotation energy back to the bus occurs (counter-intuitively) during a low torque deceleration from high speed. In this case, the resistive losses in the motor are low. If mechanical drag is low, much of the stored rotational energy is regenerated to the bus.

Bus capacitance absorbs net regenerated inductive energy from the motor winding when the drive is disabled or faulted.
The worse-case, regenerated inductive bus voltage rise is a trip of the bus over-voltage fault when decelerating the motor at full torque. Tripping the bus over-voltage fault, while stopping the flow of regenerative mechanical energy back to the bus, causes a fraction of the inductive energy stored in the windings to regenerate to the bus, causing the bus voltage to go higher than the over-voltage threshold. If there is insufficient bus capacitance to absorb this energy, the bus voltage rise is excessive and can damage the drive.

NOTE: Failure to provide adequate external capacitance on the main bus can damage the drive. The regeneration of motor inductive energy allows some pump up of the bus voltage above the bus over-voltage threshold.

Bus capacitance improves motor dynamics by holding the bus voltage stable during acceleration.
An adequately-sized bus capacitor helps provide the high peak bus current needed for rapid motor acceleration with minimum bus voltage sag. If the bus voltage sags excessively during acceleration, inverter voltage saturation occurs with loss of motor torque.

Bus capacitance lowers peak current requirements in the silicon of the power supply.
Sizing the power supply for average power, rather than peak power, lowers power supply cost and size.

In most cases, a bus capacitor does not need to be mounted close to the drive.
The inductance of the bus and ground wiring is not critical because the internal drive bus capacitance generally handles all the PWM current of the drive. A local capacitor is not needed in the following cases:

 
  • 3/9 ARMS DC S200.
  • 6/18 ARMS DC S200 with HSTemp less than 65° C.
  • 6/18 ARMS DC S200 mounted adjacent to other S200 drives with main bus supplies tied locally together. The internal bus capacitors of the adjacent drives should provide the needed capacitance.

    The exception is a single, isolated 6/18 ARMS DC S200 drive running hot (HSTemp > 65° C). In this case, connect across the bus within 1 ft of the drive, using twisted wire, a 470 µf (min), 100 V, low ESR, and an aluminum bus capacitor.

Bus capacitor for multiple drives
A conservative rule is to scale up the recommended output capacitance for one drive by the number of drives. If this value is too large, the capacitor can be calculated from energy flows. See Bus Energy & Power Numerical Examples.

NOTE: Bus capacitance can be tweaked experimentally. Increase bus capacitance if there are overvoltage trips. In general, there is sufficient bus capacitance if the bus voltage variation is ± 5 V (from 75 VDC) during the machine cycle. Check the bus voltage with an oscilloscope. Scope ground on J1-2 (Bus/Ctrl Gnd) and probe on J1-3 (+bus), Hor: 5 ms/div.

NOTE: Some bus voltage variation is normal and required for the output bus capacitor to supply or absorb energy.

Bus over-voltage fault (non-latching)
If regeneration is too high while bus capacitance is too low, the bus voltage rises to the bus over-voltage fault threshold and disables the drive transistors. It typically takes 1 to 2 ms for the motor current and torque to go to zero. After it has reached zero, there is no further rise in the bus voltage. When the bus capacitors discharge to below the over-voltage threshold by a hysteresis value, the over-voltage fault is cleared and normal operation resumes. While this protects the drive by limiting the bus voltage rise, it may not be desirable because it interrupts normal motor torque.

Unregulated power supply
External bus capacitance requirements are usually met by the output capacitor in an unregulated power supply, as long as there is no diode between the drives and bus capacitor. The same capacitor that filters the 120 Hz or 360 Hz line ripple also provides energy leveling and regeneration absorption capability.

Regulated power supply
Some regulated supplies do not tolerate an increase in voltage above the supply voltage set point. In this case, insert a diode between the positive supply terminal and the positive capacitor terminal to prevent reverse current flow into the supply. The diode should be a rectifier diode with a voltage and current rating equal to or greater than the supply.

A low ohm (< 1 Ω) power resistor between the power supply and the capacitor may be desirable. By reducing the stiffness of the voltage across the capacitor, it enhances the ability of the capacitor to supply current to the drive during motor acceleration and prevents the current limit of the regulated supply from cutting in.

Bus wire resistance
Bus wire current is the sum of DC current providing power to the drive and AC current between the drive and external capacitor. The wire between the drive and external bus capacitance should be a low enough resistance, so peak currents do not cause excessive voltage drop in the wire. Peak instantaneous bus current can be up to 25 A per drive. Size the positive Bus wiring to minimize the peak voltage drop. As a general guide, use no smaller than 16 AWG wire to span 10 feet from the drive to the shared energy leveling capacitor.

The AC and DC bus currents also flow in the Control or Bus terminal. The size of the ground wire to the drive should be no smaller than the positive Bus wire. A larger wire size yields a cleaner ground.

If a separate control supply is used, connect the control supply ground and main bus supply ground together at, or near the drives, but not at the supplies.

Bus wire inductance and bus resonance
The time domain of motor-related energy flow is measured in milliseconds. The inductive voltage drop in the bus and ground wiring for these times is small. For this reason, the energy leveling bus capacitor does not need to be located near the drive and a single bus capacitor can be shared by multiple drives.

NOTE: Be aware of bus resonance.

Current can oscillate between capacitors in any distributed DC power system with the capacitor located apart and connected in parallel with wires. The capacitors and wiring inductance form an underdamped LC circuit that can ring when excited by PWM currents.

This ringing is most easily seen by monitoring the current in the bus wiring of the drive with a current probe. The ringing occurs if the current probe shows a large (> 10 A) quasi-sinusoidal current in the 1 to 10 kHz range. While it is more difficult to see in voltage, it does cause a small sinusoidal voltage (few volts) to occur across the drive +Bus (J1-3) to Gnd (J1-2) terminals.

Occasional bursts of bus ringing are usually not too serious, but sustained or too frequent ringing is undesirable because high currents can cause heating of wires and capacitors.

The simplest way to squelch bus ringing is to lower or change the inductance of the bus wiring with the following:

 
  • Move the external bus capacitor closer to the drive.
      or
  • Twist the bus and ground wires between the drive and supply.
      or
  • Add extra capacitance (470 µf or more) near the drive bus terminals.

Recommended External Bus Capacitors
Aluminum electrolytic, computer-grade, screw top cans are available with panel mount hardware. The voltage rating should exceed the maximum bus voltage. Choose a cap with a 100 V rating for operation at 75 V bus nominal. The important capacitor parameter is capacitance (energy storage), so at 85° C, general-purpose type (see table below) is acceptable.

Panasonic G-AA Series
1.375 x 4.125 8,200 µf 100 V EEGAA2A822CKE
2 x 4.125 22,000 µf 100 V EEGAA2A223FKE
3 x 4.125 47,000 µf 100 V EEGAA2A473HKE

Cornell Dubilier DCMC Series
1.375 x 4.125 8,600 µf 100 V DCMC862U100AC2B
2 x 4.125 20,000 µf 100 V DCMC203U100BC2B
3 x 4.125 49,000 µf 100 V DCMC493U100DC2B

United Chemicon U36D Series
1.375 x 4.625 8,200 µf 100 V U36D100LG822M35X117HP
2 x 4.625 18,000 µf 100 V U36D100LG183M51X117HP
3 x 4.625 47,000 µf 100 V U36D100LG473M76X117HP

 

Two Power Supply Operation

Powering the drive control power separately from the bus power has the advantage that fault and status information is preserved when bus power is down for safety.

Wire the control supply positive terminal to J1-1 (+CTRL) and the control supply negative terminal to J1-2 (Bus/Ctrl Gnd). Wire the main supply positive terminal to J1-3 and its negative terminal to J1-2. J1-2 is a shared ground for control power and main power. Separate ground wires from the two supplies should join at or near the shared drive ground pin (J1-2).

NOTE: The drive can be damaged if the supply voltage exceeds 90 V, even briefly.

Control Supply (J1-1 to J1-2)

The voltage range of the control supply is +10 to +90 V. This supply can either be unregulated or regulated. However, it must be isolated from the power line as its negative terminal is typically earthed for safety and commoned with main power negative terminal.

For reliable starting, the control supply should have a peak power rating of at least 20 watts. A typical continuous control power drawn by an S200 DC drive is 2 to 8 watts. A single, relatively low power, low voltage supply (+12 V or +24 V) can provide control power and I/O power for multiple drives.

 

Multi-Axis Considerations

In multi-axis applications, the drive's power terminals can either be wired separately to the power supplies or paralleled locally (daisy-chained) and then wired to the power supplies. In the latter case, increase the wire size to handle the higher current.

NOTE: Locally paralleling the main power terminals of multiple drives parallels the internal bus capacitors of the drives (200 µf per drive). This allows the PWM currents of the drives to spread out, thereby lowering the temperature of the capacitor in the hottest drive.


Bus Energy & Power Numerical Examples

The energy flows in the drive bus are:

 
  • In - Motoring mechanical energy +Motor losses (motor accelerates).
  • Out - Regenerated mechanical energy –Motor losses (motor decelerates).
  • Out - Regenerated motor inductive energy (disable or fault).

Min. External Bus Capacitance

Inductance in AKM motors mated to S200s can be as high as 5 mH (line-to-line). The inductive energy stored in a 5 mH motor at 18 ARMS is calculated as:
       E winding = 0.75 x Inductance line-to-line x IRMS x IRMS
                      = 0.75 x 0.005 henry x 18 RMS x 18 RMS
                      = 1.2 joules

The bus capacitor needed to absorb the regenerated energy (EREGEN) is sized using the general rule that the energy stored in the capacitor be a minimum of 5 * EREGEN. This limits the voltage increase on the bus due to regeneration to 10% of the DC value. Using this general rule to find the minimum bus capacitance for the motor in the above example (for simplicity, ignore that a fraction of regenerated inductive energy is dissipated in the motor):
       E bus cap = 5 x 1.2 joules = 6 joules
       E bus cap = 1/2 Cbus x DC voltage x DC voltage

Assuming that the bus DC voltage is 75 volts:
       Cbus = 2 x Ebus cap/(75 V x 75 V)
               = 2 x 6 joules/(75 V x 75 V)
               = 2,133 µF
The internal S200 bus capacitance is 200 µf, which is less than 10% of the required capacitance for energy absorption.

Energy from Acceleration Time

The bus supply for a group of S200 drives must have enough total capacitance to handle brief, high-current bus transient flows (positive and negative) a few milliseconds without excessive bus voltage variation. The peak output power of a 6/18 ARMS DC S200 can be as high as 1.5 kW (1.5 kW = 18 ARMS x rt(2) x 60 V (emf + IR)). This is an energy flow of 3 joules for 2 ms or 15 joules for 10 ms.

Mechanical energy is estimated by considering the load to be pure inertia and measuring the velocity transition times. A full torque acceleration or deceleration of an inertia load yields a triangle power pulse with an energy (in joules) half of the peak power (in watts) multiplied by the velocity ramp time (in seconds) from zero speed. Motor acceleration can be monitored by mapping velocity and torque to DAC monitor pins (J4-14, 15) and looking at them with a scope. Set DM1Map to VelFB and DM2Map to IFB. See the I/O Setting tab in S200 Tools. At a peak power flow to the shaft of 1 kW = (25 A x 40 V EMF), the energy delivered vs acceleration time is:
       5 ms          2.5 joules
       10 ms        5.0 joules
       15 ms        7.5 joules

Capacitor Energy Absorb/Deliver

The capacitor energy absorbed or delivered for a 5 V change from a 75 bias is:
       3 joules for 8,000 µf
       7 joules for 20,000 µf
       16 joules for 45,000 µf

Bus DC Input Power

Bus input power can be estimated by adding motor shaft power and motor resistive winding loss. The shaft power equation is:
       Shaft power (watt) = Torque (N-m) x Speed (rad/sec)
              where, rad/sec = rpm/60 x 2π

The equation for motor resistive (heat) loss is:
       Winding loss (watt) = 1.5 x Rline-to-line x IRMS x IRMS

Back to Main Menu | Next

       Legal Notice  |  Tech Email  |  Feedback
      
Copyright ©
2001-2021 Motion Engineering