S200: AC Input Drives Control and Power Specifications
NOTE: Unless otherwise specified, the specifications are worse-case limits and apply over the specified operating ambient temperature and over the specified operating line voltage.
AC Control Power Supply
Parameter |
Rating |
Input Voltage Range (RMS) |
85 to 265 VAC single phase 47 to 63 Hz 120 to 375 VDC |
Ride Through Time for AC Line Drop |
85 VAC 60 Hz > 0.78 60 Hz cycles 120 VAC 60 Hz > 3.3 60 Hz cycles 240 VAC 60 Hz >18.5 60 Hz cycles |
AC Motor Power Supply
Parameter |
Rating |
Input Voltage Range (RMS) |
90 to 265 VAC |
Phases |
1 or 3 |
Transformer Suggested KVA |
S20260: 1.5 to 2 kVA S20360: 2.0 to 3 kVA S20660: 3.0 to 5 kVA |
Maximum AC Line KVA1 |
100 |
AC Bus Voltage and Faults
Parameter |
Rating |
240 VAC Input Nominal Bus Voltage |
320 VDC |
| 120 VAC Input Nominal Bus Voltage | 155 VDC |
| BUS Undervoltage Fault | Factory Default is None |
| BUS Overvoltge (BusOV) Fault | 407 VDC ± 5% |
BUS Regen Voltage |
= 0.974 * BusOV = 397 VDC Nominal |
AC Inrush Current and Fusing
Parameter |
S20260 |
S20360 |
S20660 |
Worse Case Inrush Peak Current at 240 VAC |
140 A 0-p | 140 A 0-p | 240 A 0-p |
| Inrush pulse width | 1.5 ms | 1.5 ms | 2.0 ms |
Recommended Fusing Line Inputs
Parameter |
S20260 |
S20360 |
S20660 |
Type – 250 VAC Time Delay Fuse |
|||
| 240 VAC 3 Phase (ARMS) | Bussmann MDA-5 | Bussmann MDA-8 | Bussmann MDA-15 |
| 240 VAC 1 Phase (ARMS) | Bussmann MDA-5 | Bussmann MDA-10 | Bussmann MDA-20 |
| 120 VAC 1 Phase (ARMS) | Bussmann MDA-5 | Bussmann MDA-10 | Bussmann MDA-20 |
AC Control Inrush Current and Fusing
Parameter |
Rating |
Worse Case Inrush Peak Current at 240 VAC |
10 A 0-p |
| Inrush Pulse Width | 1.60 ms |
| Fusing – Control Inputs | Bussmann MDA – 1/2 |
AC Power on Delay
Parameter |
Rating |
Control Power Applied to Drive Operational |
1.25 sec |